AC Clamp Meter TES-3040
Quantity
Product Features
- 3-3/4 Digital LCD with bar-graph.
-
Auto-Ranging on Volt, Ohm, Current,
Frequency measurements. - Auto-power off.
- Data Hold mode.
- MAX/MIN Hold mode.
- Zero/Adjustment/Relative Reading.
DC Voltage(Autorange & Manual)
Range | Resolution | Accuracy | Input Impedance | Overload protection |
400mV | 0.1 mV | ±(0.75%rdg+2dgts) | ≧1000MΩ | 660Vrms |
4V | 0.001V | ≒ 11MΩ | ||
40V | 0.01V | ≒ 10MΩ | ||
400V | 0.1V | |||
600V | 1V |
Range | Resolution | Accuracy | Input impedance | Overload protection |
Frequency Response |
4V | 0.001V |
±(1.2%rdg +5dgts) |
≒ 11MΩ | 660Vrms | 40~450Hz |
40V | 0.01V | ≒ 10MΩ | |||
400V | 0.1V | ||||
600V | 1V |
±( 1.5%rdg + 5dgts) |
Range | Resolution | Accuracy | Overload protection |
Frequency Response |
400A | 0.1A |
±( 2%rdg + 10 dgts ) |
1100A | 40~450 Hz |
1000A | 1 A |
Range | Resolution | Accuracy | Sensitivity | Overload protection |
100 Hz | 0.01 Hz | ±( 0.5%rdg+5dgts) | 5A | 1100A |
1KHz | 0.1 Hz |
Range | Resolution | Accuracy | Sensitivity | Overload protection |
100 Hz | 0.01 Hz | ±( 0.1%rdg+2dgts) | 100mV | 660Vrms |
1KHz | 0.1 Hz | |||
10KHz | 0.001KHz | |||
100KHz | 0.01 KHz | |||
800KHz | 0.1 KHz | 1V |
Range | Resolution | Accuracy |
Open circuit Voltage |
Overload protection |
400Ω | 0.1Ω | ±( 1%rdg+5dgts) | ≦0.5 VDC | 660Vrms |
4KΩ | 0.001KΩ | ±( 1%rdg+3dgts) | ||
40KΩ | 0.01 KΩ | |||
400KΩ | 0.1 KΩ | |||
4MΩ | 0.001MΩ | |||
40MΩ | 0.01 MΩ | ±( 1.5%rdg+3dgts) |
Range | Continuity beeper | Open Circuit Voltage | Overload protection |
≦40Ω | ≦0.5V | 660Vrms |
Range | Resolution | Accuracy | Overload protection |
0.001V | ±( 1%rdg+2dgts ) | 660Vrms |
SPECIFICATIONS
Numerical Display :3 3/4 digit liquid crystal display (LCD) maximum reading 3999.
Range Selection :All ranges are selected by a single range switch.
Over Range Indication:LCD will show a "4" flashing in the highest position accompanied with a
continuous beeping. (except for ranges of 1000A AC , and 600VDC 600VAC ).
LowBattery Indication:The is displayed when the battery voltage drops below the operating voltage.
Sampling Rate : 20 times/sec ( Barograph ) 2 times/sec (Digital Display)
Power Source :one 006p 9V or IEC 6F22or NEDA 1604 Battery.
Battery Life :300hr approx. (Alkaline)
Polarity :Automatic polarity "–" display for negative input.
Auto power off time :Approx. 30 minutes.
Operating Temperature:0℃ to 50℃
and Humidity (32℉ to 122℉) below 80%RH
StorageTemperature :-10℃ to 60℃ and Humidity (14℉ to 140℉) below 70%RH
Dimensions :239(L)x66(W)x34(H)mm
Weight :Approx. 430g