Digital Earth Tester TES-1700
Quantity
Product Features
- Capable of measuring earth voltage.
- Data hold , MAX / MIN function.
-
Auto power off function:
The timer operates automatically about 3 minutes when the " Test Button Switch " are pressed to keep the tester power on. - 2mA measuring current permits earth resistance tests without tripping earth leakage current breakers in the circuit under test.
- In addition to the facility for precision measurement, test leads for simplified two wire measuring system also supplied as standard accessories.(unit can be hung from the neck for simplified measurement).
- Automatic warning when resistance of auxiliary earth. Spikes is in excess of tolerance.
- Designed to meet IEC1010-1 safety standard.
Measuring Range and Accuracy ( at 23℃ and 45-75%RH )
Function | Measuring range | Accuracy | Overload Protection |
Earth Voltage | 0 ~ 399.9V (50Hz, 60Hz) | ±(1%rdg+4dgts) | 400Vrms / 1 minute |
Earth Resistance | 0 ~ 39.99Ω | ±(2%rdg+0.2Ω) | 250Vrms / 10 seconds |
0 ~ 399.9Ω | ±(2%rdg+3dgts) | ||
0 ~ 3999Ω |
Current Consumption ( typical Value with battery voltage of 12V )
Range | ON |
40Ω/ 400Ω/4000Ω | 58mA |
Earth V | 22mA |
General Specification:
Safety Standard | IEC1010-1 overvoltage category Ⅲ, IEC 61557 |
Display | 3-3/4 digit liquid crystal display with a maximum reading of 3999. |
Timer (Auto power off) | about 3 minutes. |
Dimensions | 190x140x77mm |
Weight | Approx. 800 (with battery) |
Power Source | Eight 1.5V 01t AA Size Battery. |
Over range Indication | “ OL ” will be shown on the LCD Penal when out of range measurement is made. |
Operating Temperature and Humidity | 0 to 40°C (32 to 104°F) , below 80% RH |
Storage Temperature | -10 to 60°C (14 to 140°F) |
Accessories | Test leads 1 set, Auxiliary earth spikes 4 piece, Battery 8 piece, Carrying case, Neck strap, Manual. |